Panchayat:Repo18/Law Manual Page1154: Difference between revisions
(Created on 25.01.2019) |
No edit summary |
||
Line 16: | Line 16: | ||
{| class="wikitable" | {| class="wikitable" | ||
|- | |- | ||
| '''Parameter (1)''' || '''(2)''' || Emission Standard (3) | | '''Parameter (1)''' || '''(2)''' || '''Emission Standard (3)''' | ||
|- | |- | ||
| Particulates || 50 mg/Nm3 || Standard refers to half hourly average value | | Particulates || 50 mg/Nm3 || Standard refers to half hourly average value |
Latest revision as of 05:13, 25 January 2019
15 | Nickel (as Ni), mg/l, max | 3.0 | 3.0 | - |
16 | Cyanide (as CN), mg/l, max. | 0.2 | 2.0 | 0.2 |
17 | Chloride (as CI), mg/l, max. | 1000 | 1000 | 600 |
18 | Fluoride (as F), mg/l, max | 2.0 | 1.5 | - |
19 | Phenolic compounds (as CH,OH) mg/l, max. | 1.0 | 5.0 | - |
Note: While discharging treated leachates into inland surface waters, quantity of leachates being discharged and the quantity of dilution water available in the receiving water body shall be given due consideration.
C. Standards for incineration:— The Emission from incinerators /thermal technologies in Solid Waste treatment/disposal facility shall meet the following standards, namely:
Parameter (1) | (2) | Emission Standard (3) |
Particulates | 50 mg/Nm3 | Standard refers to half hourly average value |
HCI | 50 mg/Nm3 | Standard refers to half hourly average value |
SO2 | 200 mg/Nm3 | Standard refers to half hourly average value |
CO | 100 mg/Nm3 | Standard refers to half hourly average value |
50 mg/Nm3 | Standard refers to daily average value | |
Total Organic Carbon | 20 mg/Nm3 | Standard refers to half hourly average value |
HF | 4 mg/Nm3 | Standard refers to half hourly average value |
NOX (NO and NO2 expressed as NO2) | 400 mg/Nm3 | Standard refers to half hourly average value |
Total dioxins and furans | 01 ng TEQ/Nm3 | Standard refers to 6-8 hours sampling. Please refer guidelines for 17 concerned congeners for toxic equivalence values to arrive at total toxic equivalence |
Cd + Th + their compounds | 0.05 mg/Nm3 | Standard refers to sampling time anywhere between 30 minutes and 8 hours. |
Hg and its compounds | 0.05 mg/Nm3 | Standard refers to sampling time anywhere between 30 minutes and 8 hours |
Sb + As + Pb + Cr + Co + Cu + Mn + Ni + V + their compounds | 0.5 mg/Nm3 | Standard refers to sampling time anywhere between 30 minutes and 8 hours. |
Note.- All values corrected to 11% oxygen on a dry basis. |
Note:
(a) Suitably designed pollution control devices shall be installed or retrofitted with the incinerator to achieve the above emission limits.
(b) Waste to be incinerated shall not be chemically treated with any chlorinated isinfectants. (c) Incineration of chlorinated plastics shall be phased out within two years. (d) if the concentration of toxic metals in incineration ash exceeds the limits specified in the Hazardous Waste (Management, Handling and Trans boundary Movement) Rules, 2008, as amended from time to time, the ash shall be sent to the hazardous waste treatment, storage and disposal facility. (e) Only low sulphur fuel like LDO, LSHS, Diesel, bio-mass, coal, LNG, CNG, RDF and bio-gas shall be used as fuel in the incinerator. (f) The CO2 concentration in tail gas shall not be more than 7%.
ഈ താൾ 2018 -ലെ പഞ്ചായത്ത് റെപ്പോ നിർമ്മാണം യജ്ഞത്തിന്റെ ഭാഗമായി സൃഷ്ടിച്ചതാണ്. |